Event magnitude
85.22%
of nominal voltage
Duration
0.017 s (about one 60 Hz cycle)
- Trigger channel
- L1-N
- Trigger threshold
- 90.0% of nominal
- Nominal
- 120 / 208 V
- Meter
- P3001520
A brief dip below 90% of nominal voltage on one or more phases. The power stayed on; equipment may have flickered. A sag is a brief dip, not an outage: the lights may have flickered, but power stayed on.

RMS plot and per-channel readings

| Channel | Min | Max | Min (event) | Max (event) |
|---|---|---|---|---|
| N-E | 0.07V | 0.07V | 0.07V | 0.07V |
| L1-N | 102.3V | 121.6V | 102.3V | 112.5V |
| L2-N | 120.3V | 133.7V | 127.7V | 133.7V |
| L3-N | 120.5V | 122.3V | 121.5V | 122.3V |
| L1-L2 | 202.0V | 209.1V | 202.0V | 205.5V |
| L2-L3 | 209.1V | 209.9V | 209.1V | 209.5V |
| L3-L1 | 208.1V | 210.1V | 208.1V | 209.4V |
| L1 | Amp | 11.59A | 17.96A | 11.59A |
| L2 | Amp | 11.73A | 17.44A | 12.92A |
| L3 | Amp | 7.77A | 11.09A | 7.77A |
| N | Amp | 6.85A | 14.07A | 8.77A |
| L6 | Amp | 4.880A | 5.819A | 4.880A |
| L7 | Amp | 4.834A | 5.774A | 4.834A |
| L8 | Amp | 2.406A | 3.987A | 2.406A |
| Frequency | 60.000Hz | 60.020Hz | 60.000Hz | 60.011Hz |
| Power | 3.429kW | 3.988kW | 3.429kW | 3.988kW |